R-3200C
R-3200C
R-3200C
R-3200C
R-3200C
R-3200C
+
  • R-3200C
  • R-3200C
  • R-3200C
  • R-3200C
  • R-3200C
  • R-3200C

R-3200C


        Digital Input Module

Product Features:
·Power Supply and Signal Isolation

·Connection is stable

·Compact size saves more installation space

·Optional piercing-type or spring-loaded terminals available to save wiring time.

Business Data
Order Number Model Specifications
40003050  R-1600C R Series Digital Input Module, 16-Channel, PNP/NPN 24VDC, Diagnostic Function, Spring-Loaded Terminal
40003066  R-1600C/IDC R Series Digital Input Module, 16-Channel, PNP/NPN
24VDC, Diagnostic Function, Piercing Terminals
40003055  R-3200C R Series Digital Input Module, 32 Channels, PNP/NPN
24VDC, Diagnostic Function, Spring-Loaded Terminal
40003067  R-3200C/IDC R Series Digital Input Module, 32 Channels, PNP/NPN
24VDC, Diagnostic Function, Piercing Terminals
40003079  R-1600C-A R Series Digital Input Module, 16-Channel, PNP/NPN
24VDC, Diagnostic Functionality, Spring-Loaded Terminals (No Diagnostic Byte)
40003089  R-1600C/IDC-A R Series Digital Input Module, 16-Channel, PNP/NPN
24VDC, Diagnostic Functionality, Piercing Terminals (No Diagnostic Byte)
40003084  R-3200C-A R Series Digital Input Module, 32 Channels, PNP/NPN
24VDC, Diagnostic Functionality, Spring-Loaded Terminals (No Diagnostic Byte)
40003090  R-3200C/IDC-A R Series Digital Input Module, 32 Channels, PNP/NPN
24VDC, Diagnostic Functionality, Piercing Terminals (No Diagnostic Byte)
     
Basic Parameters
Model R-1600C R-3200C
Protection Rating IP20
Dimensions (L × W × H) 104×12×86mm 104×24×86mm
Weight 72.5g 140g
Operating Temperature -25℃..70℃
Operating Humidity 5%.….95%
Operating Atmospheric Pressure 80KPa...106KPa
   
Technical Specifications
Input Type Digital Input
Input Method PNP/NPNT ype
Input Channel 16  32 
Input Process Data 4 Byte 6 Byte
Input Process Data (Without Diagnostic Byte) 2 Byte 4 Byte
“0” Signal PNP mode: -3 ~ 5V NPN mode: 11 ~ 30V
“1” Signal PNP mode: 11~30V NPN mode: -3~5V
Software Filtering Time Support
Diagnostic Upload Support
Hot Swap Support
Overvoltage/Short-Circuit Protection Support
Isolation Optocoupler Isolation
Static Operating Current ≤100mA
   
Indicator light
RUN(CO) Red Red Red Alternating red and green flashes Green Green
ERR(C1) Red extinguish extinguish extinguish Red Green
Status Power-on not initialized Reinitializing Internal Bus Timeout Module Matching Failure Functional failure Normal operation
I0 Green: Channel signal normal Red: Channel signal abnormal

Previous Page

Next Page

Previous Page

Next Page

Accessories Instruction

Related Accessories