R-AIO4-VI
| Analog Module Product Features: ·Power Supply and Signal Isolation ·Connection is stable ·Compact size saves more installation space ·Spring-loaded terminals, saving wiring time |
|||||
| Business Data | |||||||
| Order Number | Model | Specifications | |||||
| 40003060 | R-AIO4-VI | R Series Analog Modules, 4-Channel, Current/Voltage, Diagnostic Functionality, 0–20 mA, 4–20 mA, 0–5 V, 0–10 V, 5–10 V DC |
|||||
| Basic Parameters | |||||||
| Model | R-AIO4-VI | ||||||
| Protection Rating | IP20 | ||||||
| Dimensions (L × W × H) | 104×12×86mm | ||||||
| Weight | 72.5g | ||||||
| Operating Temperature | -25℃...70℃ | ||||||
| Operating Humidity | 5%.…95% | ||||||
| Operating Atmospheric Pressure | 80KPa...106KPa | ||||||
| Technical Specifications | |||||||
| Input/Output Type | Analog Input/Output | ||||||
| Input/Output Method | Current and Voltage Input/Output | ||||||
| Analog Channel | 4 | ||||||
| Input Process Data | 10 Byte | ||||||
| Output Process Data | 8 Byte | ||||||
| Current Input/Output Range | 0~20mA;4~20mA | ||||||
| Voltage Input/Output Range | 0~5V;0~10V;5~10V DC | ||||||
| Configuration Functions | Each channel's input/output, current/voltage can be individually configured. | ||||||
| Input/Output Error | ±0.3% of full scale | ||||||
| Number of Filter Passes | 0-30(Default0) | ||||||
| Measurement Display Format | 16-bit unsigned integer or dimensioned data *1000 | ||||||
| Resolution | Input 16 bits, output 13 bits | ||||||
| Factory Settings | Port not in use | ||||||
| Ripple | <1% | ||||||
| Diagnostic Upload | Support | ||||||
| Hot-Swap | Support | ||||||
| Overvoltage/Short-Circuit Protection | Support | ||||||
| Isolation | Optocoupler Isolation | ||||||
| Static Operating Current | ≤100mA | ||||||
| Expansion Module Indicator Light | |||||||
| RUN(CO) | Red | Red | Red | Alternating red and green flashes | Green | Green | |
| ERR(C1) | Red | extinguish | extinguish | extinguish | Red | Green | |
| Status | Power-on not initialized | Reinitializing | Internal Bus Timeout | Module Matching Failure | Functional failure | Normal operation | |
| I0 | Green: Channel signal normal Red: Channel signal abnormal | ||||||
Accessories Instruction