S-Al4-TC
| Temperature Measurement Module Product Features: ●Power Supply and Signal Isolation ●Connection is stable ●Compact size saves more installation space ●Spring-loaded terminals, saving wiring time |
||||||
| Business Data | ||
| Order Number | Model | Specifications |
| 40002089 | S-Al4-TC | S Series Temperature Module, 4-Channel, Thermocouple Diagnostic Capabilities, J/K/E/N/R/S/B/T |
| 40002090 | S-Al4-PT | S Series Temperature Module, 4-Channel, RTD Diagnostic Functionality, PT100/PT500/PT1000 |
| Basic Parameters | ||
| Model | S-Al4-TC | S-Al4-PT |
| Protection Rating | IP20 | |
| Dimensions (L × W × H) | 104×12×86mm | |
| Weight | 72.5g | |
| Operating Temperature | -25°℃...70℃ | |
| Operating Humidity | 5%.…95% | |
| Operating Atmospheric Pressure | 80KPa.…106KPa | |
| Technical Specifications | ||
| Input Type | Thermocouple Input | Thermoresistor Input |
| Input Channel | 4 | |
| Input Process Data | 18 Byte | 16 Byte |
| Input Type | J/K/E/N/R/S/B/T | PT100/PT500/PT1000 |
| Wiring Method | Second-tier/Third-tier/Fourth-tier | |
| Filter Order | 0-10 (default 0) | |
| Resolution | 16 bit | |
| Measurement Error | J/E/N/R/S/B:<±2℃ K:-200℃~0℃<±3℃,0℃~1300℃<±2℃ T:-250℃~0℃:<±0.7%,0℃~400℃:<±0.2% |
PT100/PT500/PT1000 Two-wire: <±0.3% Others: <±0.2% |
| Function Settings | Wire break detection (resets measurement value upon breakage) Upper/lower limit detection Upper/lower threshold setting |
|
| Diagnostic Upload | Support | |
| Factory Settings | Port not in use | |
| Overvoltage/Short-Circuit Protection | Support | |
| Isolation | Optocoupler Isolation | |
| Static Operating Current | ≤100mA | |
| Indicator light | ||
| CO | Constant off: INT Green fast flash: PRE-OP Green slow flash: SAFE-OP Green steady on: OP Off: Fault |
|
| C1 | Constant off: 24V Ua abnormal Green steady on: 24V Ua normal |
|
| A1…A4 | Corresponding channel signal is normal. | |
| B1..B4 | Corresponding channel signal is normal. | |
Accessories Instruction