IOLD20E-PA-Al8-I/1
| IO-Link Slave Analog Input Module Product Features: ●Power and Signal Isolation ●Compact size saves more installation space ●Spring-loaded terminals, saving wiring time ●Slot-mounted installation provides a stable structure and faster response times. |
||||||
| Business Data | ||
| Order Number | Model | Specifications |
| 40001104 | IOLD20E-PA-Al8-I/1 | IO-Link Slave, Analog Input Module, 8-Channel, Current, Diagnostic Function, 0–20 mA, 4–20 mA |
| 40001105 | IOLD20E-PA-Al8-V/1 | IO-Link Slave, Analog Input Module, 8-Channel, Voltage, Diagnostic Function, 0~5V, 0~10V, 5~10V DC |
| Basic Parameters | ||
| Model | IOLD20E-PA-Al8-I/1 | IOLD20E-PA-Al8-V/1 |
| Protection Rating | IP20 | |
| Dimensions (L × W × H) | 104×48×86mm | |
| Weight | 300g | |
| Operating Temperature | -25℃…70℃ | |
| Operating Humidity | 5%.…95% | |
| Operating Atmospheric Pressure | 80KPa..106KPa | |
| Technical Specifications | ||
| Input Type | Analog Input | |
| Input Method | Analog Current Input | Analog Voltage Input |
| Input Channel | 8 | |
| Input Process Data | 20 Byte | |
| Input Range | 0~20mA;4~20mA 0~5V;0~10V;5~10V DC | |
| Input Error | <±0.3% Full scale | |
| Measurement Display Format | 16 bit Unsigned integer | |
| Resolution | 16 bit | |
| Factory Settings | Port not in use | |
| Ripple | <1% | |
| Diagnostic Upload | Support | |
| Overvoltage/Short-Circuit Protection | Support | |
| Isolation | Power and Signal Isolation | |
| Static Operating Current | ≤100mA | |
| Indicator light | ||
| PWR | Green: Power supply normal | |
| IOL | Red: Communication with the main station interrupted Green flashing: Connection normal, data communication normal Green: No communication connection |
|
| MOD | Green: Normal Red: Expansion module configuration mismatch/Expansion module error |
|
| CO | Green: Power supply normal | |
| IO Signal indicator light | Green: Channel normal Red: Channel error |
|