MT67MC-PN-IOLM4A
| Ordering Information | |
| Communication Protocol | ProfiNet |
| Model | MT67MC-PN-IOLM4A |
| Order Code | 40000168 |
| Product Description | IO-LINK Master Module, 4 Class A Ports, IP67 Rating |
| I/O connection | 2×M12 D-code; 4-core holder |
| IO-Link Master Parameters |
Number of ports | 4×IO-LINK |
| IO-LINK Connection Method | M12,5 pole, A-code, female connector | |
| IO-LINK Version | 1.1 | |
| Communication Rate | COM1(4.8KBps)/COM2(38.4KBps)/COM3(230.4KBps) | |
| Port Voltage | Type.24VDC(Follow US) | |
| Port Current | 2A (following US) | |
| Class B Auxiliary Voltage | type.24VDC (following UA) | |
| Class B Auxiliary Current | 2A (following UA) | |
| Port Class | 4 × CLASS A(X1.... X4),4 × CLASS B(X5....X8) X8) | |
| Port Maximum Data Length | IN/OUT 32byte/32byte | |
| Maximum Network Distance | ≤100 meters | |
| IO-LINK Maximum Distance | ≤20 meters | |
| Digital Input/Output | 4-point PNP (input/output adaptive) | |
| Digital Inputs and outputs Parameter |
Number of inputs | Maximum 4 |
| Input Port Location | X1.... X4 | |
| Input Polarity | PNP | |
| Input signal “0” | Low level 0~5V | |
| Input signal “1” | High level 11~30V | |
| Number of outputs | Maximum 4 | |
| Output port position | X1...X4 | |
| Output polarity | PNP | |
| Output current | Single channel max. 2A | |
| Port protection | Port power short circuit protection, port overload protection | |
| Module Indicator | PWR | Green: Power supply is normal |
| Red: Module power supply is connected reversely | ||
| IO | Green: Channel signal is normal | |
| Red: Port power supply short circuit (pins 2 and 3) | ||
| LINK | Green: Link is normal, data communication is abnormal | |
| Yellow flashing: The link is normal and the data communication is normal | ||
| Off: Link not established | ||
| BUS | Green: OP status | |
| Green slow flashing: SAFEOP state | ||
| Green flashing: Pre-OP state | ||
| Off: Init state | ||
| Red and green flashing: Communication error | ||
| IO-LINK | Green: Port operational (running) status | |
| Green flashing: port is connecting | ||
| Green slow flashing: The port is in pre-operation state | ||
| Off: The port is closed. | ||
| Red: Power supply short circuit (pins 1, 3) |